Quick answer: Case water test methods use three loads that never substitute: 100 L/m²/h spray for 3 min, 1 m immersion for 30 min, and 20 kPa decay held 120 s.

Table of contents

  • Why Rain Alone Is Not Enough
  • Rain Test: Intensity, Angle, Duration
  • Immersion Test: Depth, Time, Heated Water
  • Pressure Decay and Flow Testing
  • What Each Method Actually Catches
  • Sampling Ratios and Batch Decisions
  • FAQ

1. Why Rain Alone Is Not Enough

A case that fails rain gives its leak away to a pressure rig in 30 s; a case that passes rain can still trip it. Spray is dynamic wash, immersion is static head, pressure is a differential with a gas path through the wall.

A 520 mm × 420 mm × 210 mm case projects 0.22 m², so 3 min at 100 L/m²/h delivers 1.1 L. That wets a gasket line and never fills a gap, so rain finds an uncompressed gasket, never a 0.2 mm pinhole. At 20 kPa the equivalent head is 2 m, and a slot 0.05 mm wide by 30 mm long passes enough air in 60 s to push decay past 0.3 kPa.

2. Rain Test: Intensity, Angle, Duration

Spray testing is the fastest of the case water test methods, with three variables that must be written down: intensity, angle, duration. Intensity is quoted per projected area, normally 100 L/m²/h, which is a 6.3 mm nozzle at 30 kPa; the severe setting lifts pressure to 100 kPa and flow to 100 L/min with the same bore.

Case water test methods station: black case open, foam tray with metal probes, a battery and two meters, white softbox edges at both sides
Case water test methods station: black case open, foam tray with metal probes, a battery and two meters, white softbox edges at both sides

Angle decides more than expected: run 0° and ±60° with the boom at 1 r/min and 2.5–3 m standoff, because a raised lid rib shadows the gasket at 0° and exposes it at 60°.

Duration is not fixed at 3 min: at 3 min/m² the case needs 3 min as a floor, and a wheel housing adds 1 min. Water sits at 20 ± 5 °C and within 5 °C of the case, or an 8 °C case in a 25 °C spray tests shrinkage, not sealing.

ItemStandardSevere
Intensity100 L/m²/h100 L/min
Pressure30 kPa100 kPa
Passno dropletsgain ≤2 g

3. Immersion Test: Depth, Time, Heated Water

Immersion applies static head: 10 kPa at 1 m, half the pressure rig's load, held 30 min so water creeps into micro-gaps. The closed case sinks until the lid sits 1 m below the surface at 20 ± 5 °C, then the outside is dried and the lid opened.

The heated variant simulates a swing in transit: pre-charge to 20 kPa, immerse 1 m in 65 °C water for 30 min, cool within 5 min. A vacuum forms, water is drawn toward the gasket, and the round finds a gasket that softens at 65 °C and takes a set.

Acceptance is three dry zones plus a mass check of 1 g, roughly 1 mL of water; above that the leak is continuous, not condensation, which 4 h at 40 °C and 90% RH tests separately. Depth and time move together, 2 m and 60 min for deck duty, 3 m and 24 h for subsea, every extra metre adding 10 kPa and pushing gasket compression from 25% to 35%.

4. Pressure Decay and Flow Testing

Pressure testing is non-destructive, which is why it can sit on a production line. Decay charges to 20 kPa, stabilises 30 s, then holds 120 s; 0.3 kPa or less passes, and cases above 60 L get 0.05 kPa per extra 10 L.

Case water test methods log station: black case open, foam tray with a green-wired module and cables, a grey handheld meter in the lower pocket
Case water test methods log station: black case open, foam tray with a green-wired module and cables, a grey handheld meter in the lower pocket

Flow testing runs at 5 kPa against a laminar meter and reads leak rate directly, gated at 30 mL/min; the number needs no volume compensation, but a 5 °C shop swing moves it 15%. Both routes fail first on the fixture: calibrate it empty, and if its decay exceeds 0.1 kPa, fix the fixture first.

MethodPressureCycleReadingBest use
Decay20 kPa150 skPa drop100% line check
Flow5 kPa45 smL/minFailure analysis
Bubble0.5 kPa30 sbubble positionPinpointing

5. What Each Method Actually Catches

Gasket collapse is caught by immersion only. When the lid rib stands under 1.5 mm, latch tension drops compression below 25%: 3 min of spray may not enter while 30 min of head always does, and pressure can pass the unit, because water pushes the soft gasket down while gas still finds a path.

Parting-line flash is the pressure method's home ground: a 0.05 mm fin holds a 3 min water film and cannot hold 20 kPa. Corner sink marks sit between the two: at 0.3 mm spray pools water, immersion seeps, and the rig reads normal, since a sink mark is a surface defect, not a through path.

Threaded inserts and relief valves seal on an O-ring, fail as slow seepage, and leave the gasket line merely damp after 30 min immersion. Hinge-boss warpage needs a −10 °C immersion round.

6. Sampling Ratios and Batch Decisions

Because the loads destroy or delay, case water test methods carry different sampling ratios. Decay is non-destructive at 150 s per unit and runs 100%. Rain needs foam removal and 4 h of drying, so it runs 3 units per batch. Immersion runs 1 unit per batch, for first articles and new gasket lots.

First articles get all three, to pin the mould state: cavity number, press and hold-pressure curve. Production then follows AQL 2.5 counting sampling with 13 pieces and an acceptance number of 1; two consecutive failures stop the line.

Conclusion

Treat the three methods as three sieves, not one exam taken three times. Case water test methods should end in a defect verdict: gasket collapse belongs to immersion, a through path belongs to pressure, surface wetting belongs to rain, and only a case clearing all three has earned a rating. Run all three on the first article, then 100% decay with 3 rain and 1 immersion unit per batch, and send every leak back to mould coordinates, not a tube of compound.

DefectMost sensitiveCriterionPasses anyway
Gasket collapseImmersion 1 m, 30 mingain >1 gRain 3 min
Flash 0.05 mmDecay 20 kPa, 120 sdrop >0.3 kPaRain 3 min
Corner sink 0.3 mmImmersion 1 m, 30 minpooled waterDecay normal
Valve seepageFlow 5 kParate >30 mL/minImmersion damp only

This article discusses container-side specifications and design implications only, and does not cover any handling, loading or use of the contents.

Related Reading

Related Products